Cleaning unit
Depending on the level of contamination, we recommend:
- annual visual inspection of the heat exchanger also cleaning if required.
- annual cleaning of inside.
- annual check and cleaning of condensation run-off and the siphon.
Cleaning the heat exchanger and ventilation unit
- Loosen service cover’s screws. Carefully remove service cover.
- Remove the hosing between the float switch and condensate tank.
- Remove condensate tank and crossbar.
- Loosen lateral guide rails.
- Remove punched tape on heat exchanger.
- Pull heat exchanger down and out of the unit.
- Clean heat exchanger: Vacuum the sensitive heat exchanger with a standard vacuum cleaner. Thoroughly flush enthalpy heat exchangers with water or soapy water, drip off and let them dry well.
- Replace the heat exchanger.
- Secure punched tape to fix heat exchanger in place.
- Slide lateral guide rails back against the heat exchanger and fix in place.
- Put cross bar and condensate tank back into the unit.
- Connect condensate tank with float switch of condensate lift pump.
- Check function/seal integrity of condensate tank.
- Close the central and two side service covers.
- Switch on the ventilation unit.
Whenever working on the electrical equipment on the ventilation unit, switch off the mains fuse in the fuse box and secure it against being accidentally switched back on.